You are here: Home / PRODUCTS / RCBO / SC65LE-63

loading

Share to:

SC65LE-63

· CE/CB/ISO9001/CCC certificates; · Rated voltage:230/400VAC; · frequency:50/60Hz; · Rated current:6,10,16,20,25,32,40,50,63A; · poles:1/2/3/4 optional; · Breaking Capacity:10KA;
状态:
Num:
Product Parameters


Key Words: RCBO; Miniature circuit breakers

Key Parameters:

  • CE/CB/ISO9001/CCC certificates;

  • Rated voltage:230/400VAC;

  • frequency50/60Hz;

  • Rated current:1,3,6,10,16,20,25,32,40,50,63A;

  • 1/2/3/4poles optional;

  • Mechniacal life:20,000times;

  • Flame-redardant:PA66 nylon material;

  • Protection degree:IP20;

  • With over load/short circuit protection;

  • Standard:IEC60898;

  • Enduring tem.55°C

  • Breaking Capacity:10KA;

  • Lighting/Motor protection optional


Application:

SC65LE RCBO is applied in the power system of AC 50Hz, single phase 230V, three phases 400V. When somebody gets and electric shock or the residual current exceeds the default value, the RCBO can cut off the powerautomatically to protect the personal safety and prevent the equipmentfrom the fault resulted from the residual current. It also can protect the circuit aqainst overload and short circuit or can be used for the unfrequent switch of the circuit under normal condition. And extra protection functions like over voltage, under voltage can be added according to customers' request.

It conforms to the standard IEC1009-1. GB16917.1.

Structure
SC65LE-63 series RCBO is composed of SC65-63 high breaking MCB and residual current release. This RCBO is current operating electronic RCBO, the main parts including zero sequence current transformer, electronic panel, current leakage release and the circuit breaker with protection functions of overload, short circuit.
 

Shell level rated current(A) voltage(V) Pole Rated current In(A) Rated short circuit breaking capacity Rated residual current breaking current(mA) Rated residual current no breaking current(mA) Trip time
Breaking capacity Ics(A) COSφ
63 230 1P+N 6,10,
16,20,
25,32,
40,50,
63
10000 0.75 10 5 ≤0.1S
230 2P 30 15
400 3P 50 25
400 3P+N 75 37.5
400 4P 100 50

 

Test current(A) Rated current(A) Requested time Result Start station Remark
1.13In all t>=1h Don't trip Cool
1.45In All T<1h trip heat Current ascends the requested value stably in 5s
2.55In In<=32A 1s trip Cool Auxiliary switch closed, power is on
2.55In In>32A 1s trip Cool Auxiliary switch closed, power is on
3In(Bmode) All t>=0.1s Don't trip Cool Auxiliary switch closed, power is on
5In(Bmode) All T<0.1s trip Cool Auxiliary switch closed, power is on
5In(Cmode) All t>=0.1s Don't trip Cool Auxiliary switch closed, power is on
10In(Cmode) All T<0.1s  trip Cool Auxiliary switch closed, power is on
10(Dmode) All t>=0.1s  Don't trip Cool Auxiliary switch closed, power is on
14In(Dmode) All T<0.1s trip Cool Auxiliary switch closed, power is on